The Next Code Cycle: IECC 2015 and ASHRAE 90.1-2013

The next commercial energy code cycle for most states is the IECC 2015 code and ASHRAE 90.1-2013 alternative path. For some states the new code has already gone into effect as of January 1, 2017, but the exact timing of implementation depends on each state. Remember that each state is in a code cycle, which lasts two to three years. So, theoretically, your state could switch in the next few months or in a few years. Check the status of your state energy code here.

Which States Have Made the Jump

Alabama
California
Illinois
Maine
Maryland
Massachusetts
Michigan (adopting IECC 2015/ASHRAE 2013 in April 2017)
New Jersey (adopted ASHRAE 2013)
New York
Oregon
Texas
Utah
Vermont (state-specific code modeled after IECC 2015)
Washington

Also, the new code cycle will be effective in Georgia January 1, 2018.

An Overview: IECC 2015 and ASHRAE 90.1-2013

I briefly covered this overview in a prior blog post, but it can’t hurt to go over it again, especially when it comes to complex code information. Also, note that I’m basing the upcoming changes on comparisons of the current IECC 2012 code and the ASHRAE 90.1-2010 Standard. If your state’s current code is based on the older IECC 2009 and ASHRAE 90.1-2007 Standard, you’ll see more significant envelope changes. Many states currently at the IECC 2009 code are bypassing IECC 2012 altogether (or have already done so) and adopting IECC 2015. This is a huge jump, and many metal building contractors will feel the pressure. If you haven’t used Liner Systems (Ls) or Filled Cavity/Long Tab Banded Systems (FC) in the past, you will need to start using them. Both options fulfill the metal building insulation requirements; it’s just a matter of preference. I detail the key differences between the systems below.

The choices are the same for the rest of the envelope. The building designer will have to make the decision to pursue either IECC 2015 or ASHRAE 90.1-2013. Once that decision is made, the entire building envelope, including mechanicals and lighting, must follow the same path.

Liner Systems (Ls) and Long Tab Banded Systems (FC): What’s the Difference?

First, liner systems (Ls) such as OptiLiner® are typically proprietary and, as you probably guessed, must meet ASHRAE’s requirements in order to be defined as a liner system. Long tab banded systems are usually non-proprietary and meet the specifications of a filled cavity (FC) system.

Both systems provide high-R insulation to help meet stringent energy codes. However, banded liner systems tend to achieve better U-values than long tab banded systems. Another key difference is that the OptiLiner® banded liner system is an OSHA-compliant fall protection system. Long tab banded systems typically do not offer fall protection.

As you can see in the picture on the left, the purlins are covered by the fabric vapor retarder in a banded liner system. In a long tab banded system, the purlins are exposed.

Back to the Code: Changes in Envelope Performance

There are some major changes to the envelope performance. In previous versions of the IECC code and ASHRAE Standards, it was easier to obtain lower insulation values in the roof and walls of metal buildings. The IECC 2015 and ASHRAE 90.1-2013 have the most stringent envelope requirements based on “Conditioned Space” and “Non-Residential Space”. The only option that allows minimal insulation is Semi-Heated Space within ASHRAE 90.1-2013.

Remember that:

Conditioned Space: Space that will be heated above 3.4btu’s/hr/ft2 and/or cooled (per IECC 2015).

Non-Residential Space: Spaces heated or cooled above semi-heated requirement (per ASHRAE 90.1-2013).

Semi-Heated Space: Space heated above 3.4btu’s/hr/ft2 and below 5 in climate zones (CL) 1 and 2, below 10 in CL 3, below 15 in CL 4 and 5, below 20 in CL 6 and 7 and below 25 in CL 8 (per ASHRAE 90.1-2013)

Table 3.2, which is used to determine semi-heated space, has not changed with the latest code updates.

If Semi-Heated is not allowed based on the heating system output, then each climate zone has major insulation requirement increases under the non-residential space. This is based on the ASHRAE 90.1-2013 Standard; the IECC 2015 code has, for the most part, the same values. For example, using ASHRAE 90.1-2013, climate zone 5a requires a roof U-value of .037 and a wall U-value of .050. In order to obtain these U-values, a metal building would require either a Liner System or a Filled Cavity/Long Tab System for the roof and a Liner System or Filled Cavity/Long Tab System for the walls.

An Important Update: Air Barrier Requirements

Both IECC 2015 and ASHRAE 90.1-2013 require buildings to have an air barrier in the thermal envelope, and to be indicated in drawings. The air barrier is also a checklist item on a COMcheck report. The first mention of air barriers was actually in IECC 2009. From then on, the next few code cycles made air barriers mandatory requirements.

The air barrier must be located within the building’s thermal envelope. It can be placed on the interior side, exterior side, somewhere within assemblies composing the envelope, or any combination thereof. In IECC 2015 this can be found in section C 402.5.1 and C 402.5.1.1. Exceptions include unheated buildings. In ASHRAE 90.1-2013 this can be found in sections 5.4.3, 5.4.3.1.1 and 5.4.3.1.2. Exceptions include semi-heated buildings in climate zones 1-6.

An air barrier (green material) laminated to fiberglass as part of the MaxTight system.

It is also mandatory to identify the air barrier and for it be continuous across joints and assemblies. Joints and seams must be sealed and securely installed. Penetrations and joints and seals associated with penetrations must be sealed in a manner compatible with construction material and location.

Want to make sure you don’t miss out on the latest energy code updates? Subscribe to our energy code newsletter to get blog posts sent directly to your inbox.

Sign Up For Free

MORE BLOGS

Mid-Year Energy Code Update

I’ve been on the move and traveling the country, giving energy code presentations and attending industry meetings. In this mid-year energy code update, I’m sharing the trends I’ve observed from state to state, with a focus on the challenges and opportunities the IECC 2021/ASHRAE 90.1-2019 energy code cycle poses for metal building contractors, erectors, and designers.

read more

Commercial Energy Codes & MBI: What to Know In 2023

  Happy 2023, folks. We’re kicking off the new year with something a little different: A video summary of the current energy code landscape, plus what you need to know as we move into 2023. I also cover the metal building insulation systems that meet the most...

read more

This Just In: Several States Adopt New Commercial Energy Codes

It’s officially the start of fall, folks, and you know what that means: A quick commercial energy code wrap-up. Here’s a short-and-sweet update on what’s been happening around the country. Also, are you attending METALCON? Join me for a free AIA-accredited course on...

read more

2019 Commercial Energy Codes Update

I got together with the folks at Metal Construction News and Metal Architecture to organize a webinar that will summarize the key commercial energy code information I’ve talked about over the past year.

read more